GE DS200CTBAG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - DS200CTBAG1A Seperator

Product Info
GE DS200CTBAG1A
  • Warranty. 12/18 Months

Description

TERM. BD (C)
  • Model No. DS200CTBAG1A
Repair
GE - DS200CTBAG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes DS200CTBAG1A. ICC’s highly skilled technicians have the training and expertise to repair DS200CTBAG1A. In addition, our DS200CTBAG1A repairs come with a warranty. Please fill out our Request a Quote form with DS200CTBAG1A in the Subject Line, and/or include DS200CTBAG1A in the Message, for additional information about ICC’s DS200CTBAG1A. A ICC Business Development Leader will assist you with your DS200CTBAG1A needs shortly!

Reman
GE - DS200CTBAG1A

Purchasing a remanufactured GE DS200CTBAG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - DS200CTBAG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200CTBAG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - DS200CTBAG1A

DS200CTBAG1A is an Analog Termination Module manufactured and designed by General Electric as part of the printed wiring terminal boards used in the Mark V LM Controller. The R5 core houses the Analog Termination Module (CTBA). The shaft voltage and shaft current connectors, as well as the 4-20 mA output and input, are all located on the CTBA terminal board. The CTBA board also houses the connections for IONET to the STCA board and COREBUS to the QTBA board on R1. The TCPD board in PD is connected to CTBA through the Mark V LM power source monitoring. If CTBA loses power, a bypass relay enables COREBUS to communicate.

CTBA CONNECTIONS:

8PL - Transports the IONET signals from the R5 core to the STCA board.

JAA - Carries in the R5 core the 4 20 mA outputs from the TCCA board.

JAI - If it is not in use, a termination resistor should be added. Used for the COREBUS connection.

JAJ - If it is not in use, a termination resistor should be added. Used for the COREBUS connection.

JBB - Carries the shaft voltage and current signals, as well as the 4-20 mA inputs, to the TCCA board in the R5 core.

JEE - Connects the STCA board in the "R5" core with the COREBUS signals.

JPD - Carries in the PD core the 24 V dc power signal from the TCPD board.

JX - Connects the TCDA board in the Q51 core with the IONET signals.


CTBA HARDWARE CONFIGURATION:

BJ1 through BJ14 - Connects the respective mA input's NEG terminal to DCOM.

BJ15 - Connects the DCOM to the RS232 Monitor Port (TIMN).