GE DS200PCCAG6A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - DS200PCCAG6A Seperator

Product Info
GE DS200PCCAG6A
  • Warranty. 12/18 Months

Description

DC2000 PWR CONN
  • Model No. DS200PCCAG6A
Repair
GE - DS200PCCAG6A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes DS200PCCAG6A. ICC’s highly skilled technicians have the training and expertise to repair DS200PCCAG6A. In addition, our DS200PCCAG6A repairs come with a warranty. Please fill out our Request a Quote form with DS200PCCAG6A in the Subject Line, and/or include DS200PCCAG6A in the Message, for additional information about ICC’s DS200PCCAG6A. A ICC Business Development Leader will assist you with your DS200PCCAG6A needs shortly!

Reman
GE - DS200PCCAG6A

Purchasing a remanufactured GE DS200PCCAG6A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - DS200PCCAG6A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200PCCAG6A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - DS200PCCAG6A

DS200PCCAG6A is a Power Coupling Board manufactured by General Electric as part of the Mark V Series used in gas turbine control management systems. This is one of several versions of power connect cards available from Control Systems. The PCCA uses pulse transformers to provide gate drive to the SCR bridge. For low, to medium horsepower controllers, the PCCA also includes snubber circuits to control spikes across the ac lines, dc bus, and gate drivers.
DS200PCCAG6A Features
The Power Connect Card connects the drive's control circuitry to the SCR power bridge. The PCCA board provides gate drive to the SCR bridge via pulse transformers. The PCCA board includes snubber circuits to control spikes across the ac lines, dc bus, and gate drivers for low-to-medium horsepower controllers. Some or all of the snubber circuits are omitted from the board for higher horsepower controllers and are located elsewhere in the system.

DS200PCCAG6A Application Data
Board Hardware
The board includes configurable jumpers and wiring plug connectors (but no LEDs, fuses, testpoints, or switches).

Configurable Jumpers (JP and WP)
JP1, JP2, WP3, and WP4 wire jumpers are located on the PCCA board. Jumpers JP1 and JP2 must be connected to the stab terminals P3 through P10 that correspond to the card group number and system voltage.
WP3 and WP4 jumpers are used to connect stab terminals P2A and P2B, and P1A and P1B, respectively. These jumpers determine whether the PCCA snubber capacitors are connected to the same power bridge point as the voltage feedback channel.

Board Connectors
JP1, JP2, WP3, and WP4 wire jumpers are located on the board. Jumpers JP1 and JP2 must be connected to the stab terminals P3 through P10 that correspond to the card group number and system voltage. WP3 and WP4 jumpers are used to connect stab terminals P2A and P2B, and P1A and P1B, respectively. These jumpers determine whether the PCCA snubber capacitors are connected to the same power bridge point as the voltage feedback channel.

DS200PCCAG6A Replacement Procedure
Turn off the drive and wait several minutes for all of the capacitors to discharge. Before touching any electrical circuits, make sure the power is turned off.
Open the cabinet door on the equipment to gain access to the printed wiring boards.
This reveals the drive controller card, which is visible from the front (in the front board carrier).
The PCCA board is mounted behind the drive control on the back of the board carrier (the power supply board is mounted on the front).
Lift the front board carrier (with the drive control card) and tilt it forward and down by pulling the lock tabs on either side of the board rack.
To access the board, lift the second board carrier (with the power supply board) and tilt it forward and down.
Disconnect all cables from the PCCA board with care as follows:
For ribbon cables, grasp each side of the cable connector that mates with the board connector and gently pull the cable connector free
For pull-tab cables, carefully pull the tab.
Release the PCCA board from the board carrier by pushing back on the six plastic snaps (holders).
Double-check that all jumpers on the new (replacement) PCCA board are in place.