GE DS200TBQAG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - DS200TBQAG1A Seperator

Product Info
GE DS200TBQAG1A
  • Warranty. 12/18 Months

Description

TERM.BD (C)R-S-T TC I/O
  • Model No. DS200TBQAG1A
Repair
GE - DS200TBQAG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes DS200TBQAG1A. ICC’s highly skilled technicians have the training and expertise to repair DS200TBQAG1A. In addition, our DS200TBQAG1A repairs come with a warranty. Please fill out our Request a Quote form with DS200TBQAG1A in the Subject Line, and/or include DS200TBQAG1A in the Message, for additional information about ICC’s DS200TBQAG1A. A ICC Business Development Leader will assist you with your DS200TBQAG1A needs shortly!

Reman
GE - DS200TBQAG1A

Purchasing a remanufactured GE DS200TBQAG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - DS200TBQAG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200TBQAG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - DS200TBQAG1A

core to the TCCA board in the R5> core.\n\nTHERMOCOUPLE INPUTS:\n\nThree groups of 15 people each make up the TBQA terminal board, one group for each core, and each group has its own solid-state cold junction compensation. Typically, control and trip purposes are handled by the thermocouple inputs. 42 thermocouples that are mounted on a TBQA terminal board inside the R5 core can be monitored by the R5 controller. Three groups of fourteen inputs each having a distinct solid-state cold junction correction make up this group of inputs. R5 inputs are usually solely used for monitoring; they are never utilized for control or trip."}" data-sheets-userformat="{"2":12418,"4":{"1":2,"2":16777215},"10":2,"15":"Calibri","16":11}" style="font-size: 11pt; font-family: Calibri, Arial;">DS200TBQAG1A is a Thermocouple Termination Module manufactured and designed by General Electric as part of the Mark V LM Series used in gas turbine control systems. The R1 and R5 cores contain the TBQA (Thermocouple Termination Module). 45 thermocouple input signals can be received by the TBQA terminal board. The TBQA in R1 distributes its input signals in the following ways: 15 signals (thermocouples #1 through #15) go to the TCQA in R1, 15 signals (thermocouples #16 through #30) go to the TCQA in the core of R2, and 15 signals (thermocouples #31 through #45) go to the TCQA in R3. 42 thermocouple input signals are connected to the TCCA board in "R5" and can be received by the TBQA board in "R5". The circuits for compensating for cold junctions are likewise provided by the TBQA board.

TBQA CONNECTIONS:

JAR - Writes the cold junction signal and the thermocouple signals #1 through #15 to the TCQA board in the core. The thermocouple signals #1 through #15 and the cold junction signal are written to the TCCA board in the core from the core.

JAS - Writes the cold junction signal and thermocouple signals #16 through #30 to the TCQA board in the core. The thermocouple signals #16 through #30 and the cold junction signal are written to the TCCA board in the core from the core.

JAT - Thermocouple signals #31 through #45 and a cold junction signal are written to the TCQA board in the 'R3' core from the 'R1' core. The thermocouple signals #31 through #42 and the cold junction signal are written from the R5> core to the TCCA board in the R5> core.

THERMOCOUPLE INPUTS:

Three groups of 15 people each make up the TBQA terminal board, one group for each core, and each group has its own solid-state cold junction compensation. Typically, control and trip purposes are handled by the thermocouple inputs. 42 thermocouples that are mounted on a TBQA terminal board inside the R5 core can be monitored by the R5 controller. Three groups of fourteen inputs each having a distinct solid-state cold junction correction make up this group of inputs. R5 inputs are usually solely used for monitoring; they are never utilized for control or trip.