GE DS200TBQBG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - DS200TBQBG1A Seperator

Product Info
GE DS200TBQBG1A
  • Warranty. 12/18 Months

Description

TERM BD(R-S-T) ANALOG I/O
  • Model No. DS200TBQBG1A
Repair
GE - DS200TBQBG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes DS200TBQBG1A. ICC’s highly skilled technicians have the training and expertise to repair DS200TBQBG1A. In addition, our DS200TBQBG1A repairs come with a warranty. Please fill out our Request a Quote form with DS200TBQBG1A in the Subject Line, and/or include DS200TBQBG1A in the Message, for additional information about ICC’s DS200TBQBG1A. A ICC Business Development Leader will assist you with your DS200TBQBG1A needs shortly!

Reman
GE - DS200TBQBG1A

Purchasing a remanufactured GE DS200TBQBG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - DS200TBQBG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200TBQBG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - DS200TBQBG1A

DS200TBQBG1A is an Input Termination Module developed by General Electric. The R2 and R3 cores each have a seventh position, which is the Input Termination Module (TBQB). The TCQA and TCQC boards in the R1 core are coupled with the TBQB terminal board in the R2 core. The TCQA and TCQC boards in the R3 core are linked to the TBQB terminal board there. The TBQB terminal board receives the input signals for voltage, vibration, and pulse rate.

DS200TBQBG1A Connections
JGR - Writes the analog current, voltage, and vibration signals to the TCQA board in the appropriate cores.
JHR - Writes the compressor stall detection and pulse rate inputs to the TCQC board in the appropriate cores.
JGS/T - Not frequently used.
JHS/T - Not frequently used.
Hardware Configuration
BJ1 through BJ4 - Used in older applications to fan out the pressure transducer #1 input signal (compressor stall detection).
Used in conjunction with BJ1 through BJ4 are BJ5 through BJ7. Install a burden resistor so that the pressure transducer #1's input signal is converted from a voltage signal to a mA signal.
BJ8 through BJ15 - Sets the current or voltage for analog inputs.