ANALOG I/O BOARDICC’s large inventory investment includes DS200TCCAG1B. ICC’s highly skilled technicians have the training and expertise to repair DS200TCCAG1B. In addition, our DS200TCCAG1B repairs come with a warranty. Please fill out our Request a Quote form with DS200TCCAG1B in the Subject Line, and/or include DS200TCCAG1B in the Message, for additional information about ICC’s DS200TCCAG1B. A ICC Business Development Leader will assist you with your DS200TCCAG1B needs shortly!
Purchasing a remanufactured GE DS200TCCAG1B offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.
Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200TCCAG1B and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty
DS200TCCAG1B is a Common Analog I/O Board developed by GE under Mark V series. The CTBA, TBQA, and TBCA terminal boards positioned in the R5 core send analog signals to the Common Analog I/O Board (TCCA), which is situated in the R5 core. 420 mA inputs and outputs, RTD inputs, thermocouple inputs, shaft voltage inputs, and shaft current inputs are some of the signals that make up this group. Through the 3PL connector, the signals are written to the STCA board.
DS200TCCAG1B Configuration
Hardware On the board, there are three hardware jumpers labeled J1, JP2, and JP3. The serial RS232 port can be enabled or disabled using J1. For card testing, the oscillator is turned off using JP2. For factory testing, JP3 is used.
Software The HMI's I/O Configuration Editor is where the settings for the thermocouples, RTDs, mA inputs and outputs, and shaft voltage and current are entered.
4-20 mA TCCA Input Circuit
The circuitry for the 4-20 mA input signals is provided by the board. Through the JBB connector, the signals are read from the CTBA terminal board. The voltage drop is measured by the board and written to the I/O Engine via the 3PL connector as the transducer current is reduced across a burden resistor.
4-20 mA Output Circuit for TCCA
The circuitry for driving 420 mA outputs to the CTBA terminal board via the JAA connector is provided by the board. Typically, these signals are utilized to power distant instruments for monitoring.
RTD Circuit TCCA
The circuitry that draws excitation for the RTDs from the TBCA terminal board. When the temperature varies, the resistance changes, causing the voltage on the RTD to change. A constant current is fed through the RTD. The voltage signal is measured, scaled, and adjusted by the board. The board reads the RTD signals from the TBCA terminal board via the JCC and JDD connectors. The 3PL connector is used to transmit the signals to the I/O Engine. I/O configuration constants are used to choose the kind of RTD.
DS200TCCAG1B Thermocouple Circuit
The TBQA terminal board reads the thermocouple inputs. The cold junction circuitry on the TBQA terminal board produces the cold junction signals. It computes the cold junction compensation using these variables. The actual temperature read by the thermocouple is determined using the thermocouple input and compensation value. Through the 3PL connector, the I/O Engine reads the value. I/O configuration constants are used to choose the types and curves of thermocouples.
Shaft Monitoring
The board is in charge of monitoring the voltage and current of the turbine shaft. The JBB connector is used to read these signals from the CTBA terminal board. Through the 3PL connector, the signals are written to the I/O Engine.