Description
C EXTENDED ANALOGICC’s large inventory investment includes DS200TCCBG1A. ICC’s highly skilled technicians have the training and expertise to repair DS200TCCBG1A. In addition, our DS200TCCBG1A repairs come with a warranty. Please fill out our Request a Quote form with DS200TCCBG1A in the Subject Line, and/or include DS200TCCBG1A in the Message, for additional information about ICC’s DS200TCCBG1A. A ICC Business Development Leader will assist you with your DS200TCCBG1A needs shortly!
Purchasing a remanufactured GE DS200TCCBG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.
Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE DS200TCCBG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty
DS200TCCBG1A is a Common Extended Analog IO Board manufactured and designed by General Electric as part of the Mark V Series used in Speedtronic Gas Turbine Control Systems. The Common Extended Analog I/O Board (TCCB) scales and conditions additional analog I/O signals that are read from the TCEB board in the P1 core and the TBCB terminal board installed on the R5 core. These signals consist of the line current inputs, RTDs, generator and bus voltage inputs, and 4-20 mA/0-1 mA inputs. Through the 3PL connector, the scaled and conditioned signals are delivered to the STCA board.
CONFIGURATION:
HARDWARE: The Mark V LM's generator and bus voltage monitoring functions, as well as the line current monitoring function, are provided by the hardware jumpers J1, J2, J3, J4, and J5. The RS232 serial port is linked to DCOM through hardware jumper J14. J15 and J16 are hardware jumpers that are used for testing. For details on the hardware jumper settings for this board, consult Appendix A and the operator interface's hardware jumper panel.
SOFTWARE: The HMI's I/O Configuration Editor is where you enter the bus voltage and line current settings, as well as I/O configuration constants for the generator, mA inputs, RTDs, and other devices.