GE IS200EDCFG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - IS200EDCFG1A Seperator

Product Info
GE IS200EDCFG1A
  • Warranty. 12/18 Months

Description

BOARD - EX2100 DC FEEDBACK
  • Model No. IS200EDCFG1A
Repair
GE - IS200EDCFG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes IS200EDCFG1A. ICC’s highly skilled technicians have the training and expertise to repair IS200EDCFG1A. In addition, our IS200EDCFG1A repairs come with a warranty. Please fill out our Request a Quote form with IS200EDCFG1A in the Subject Line, and/or include IS200EDCFG1A in the Message, for additional information about ICC’s IS200EDCFG1A. A ICC Business Development Leader will assist you with your IS200EDCFG1A needs shortly!

Reman
GE - IS200EDCFG1A

Purchasing a remanufactured GE IS200EDCFG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - IS200EDCFG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200EDCFG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - IS200EDCFG1A

IS200EDCFG1A is an Exciter DC Feedback Board manufactured and designed by General Electric as part of the EX2100 Series used in Excitation Control Systems. At the SCR bridge, it detects field current and field voltage and communicates with the EISB board in the control panel through a quick fiber-optic link. High noise immunity and voltage isolation between the two boards are provided by fiber optics. Each signal travels on one of two fibers. The following are two fiber kinds that can be utilized for various distances:

Plastic-type fiber for distances up to 10 m
Hard-clad silica type for distances up to 90 m

FIELD VOLTAGE FEEDBACK:

In accordance with the kind of bridge application, the field voltage feedback circuit offers seven choice settings to reduce the bridge voltage. The bridge's negative terminal and the current shunt's positive terminal are monitored to determine the field voltage. Signals are fed into a differential amplifier, which controls a voltage-controlled oscillator after the voltage has been scaled with the jumpered resistors.

FIELD CURRENT FEEDBACK:

At the SCR bridge, the field current is measured over a DC shunt. A low-level signal with a maximum value of 500 mV is produced as a result, and it is supplied into a differential amplifier. An oscillator with voltage control receives an output voltage from the amplifier that ranges from -5 V to +5 V.

POWER SUPPLY:

EDCF receives power from an outside source which is 24 V DC. Three voltage regulators generate +15 V dc, -15 V dc, and + 5 V dc from this. The output voltages of 15 V dc operate the PSOK green LED.

APPLICATION DATA:

The EDCF has a single green LED that shows the power supply is on (PSOK). The accompanying figure, Board Layout, depicts the layout of the EDCF board.

CONNECTORS:

The board receives 24 V dc through connection J16 and the voltage across the field current shunt resistance through connector P1. The connection for the field voltage input is stab-on (E1). Through fiber-optic links, the current and voltage feedback to the control.