Description

EXCITGER H.S. RELAY DRIVER
  • Model No. IS200EXHSG3A
Repair
GE - IS200EXHSG3A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes IS200EXHSG3A. ICC’s highly skilled technicians have the training and expertise to repair IS200EXHSG3A. In addition, our IS200EXHSG3A repairs come with a warranty. Please fill out our Request a Quote form with IS200EXHSG3A in the Subject Line, and/or include IS200EXHSG3A in the Message, for additional information about ICC’s IS200EXHSG3A. A ICC Business Development Leader will assist you with your IS200EXHSG3A needs shortly!

Reman
GE - IS200EXHSG3A

Purchasing a remanufactured GE IS200EXHSG3A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - IS200EXHSG3A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200EXHSG3A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - IS200EXHSG3A

IS200EXHSG3A is an Exciter High-Speed Relay Driver Board developed by GE. It is a part of EX2100 Excitation Control and provides drivers for the DC contractors and pilot relays for D-Excitation and field flashing.

Functional Description
Through the Exciter Backplane Board, these boards connect to three Exciter Main Input/Output Boards (EMIO, redundant control) or one EMIO board (simplex control) (EBKP). On the board are pilot relays for the flashing relays 53A and 53B, as well as pilot relays for the de-excitation relay KDEP.
EXHS conditions and sends de-excitation status signals from the Exciter De-Excitation Board (EDEX) to EMIO. Crowbar status signals are conditioned on EXHS and sent to EMIO from the EXDE De-Excitation Control Board (EXDE).
On EXHS, three contact inputs from 41, 53A, and 53B are powered by 70 V dc and their feedback is monitored. The contacts are powered by the exciter power supply. The status signals generated are sent to the EMIO.
Board Replacement Procedure
Ensure that the exciter has been deactivated.
Inside the control cabinet, ensure that all electrical I/O circuits are turned off before touching them.
To simplify reconnection, ensure that all cables are labeled with the correct connector name (as marked on the board), then carefully disconnect all cables from the EXHS board.
Remove the screws holding the EXHS board to its mounting and the board itself.
Verify that the replacement board is the same type (G1 or G2) as the original one.
Install the new EXHS board on its mounting with the screws removed in step 4 and orient it in the same position as the one removed.
Reconnect all cables to the EXHS board as labeled, making sure they are properly seated on both ends. Shut the control cabinet door.
IS200EXHSG3A Application Data
The close function contactor drivers are K41 (M1, M2, C), and the flashing pilot relays are K53A and K53B.
The single de-excitation pilot relay is KDEP. J505, J508, and J515 are 25-pin connectors for cables to the EMIO boards M1, M2, and C. They carry similar signals and have similar wiring, with the exception that J505 is connected to M1, J508 is connected to M2, and J515 is connected to C.
However, J515 lacks de-excitation and crowbar signals. For auxiliary contact wetting, plugs J12M1 and J12M2 bring in 70 V dc from the M1 and M2 power supplies.