GE IS200JGNDG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - IS200JGNDG1A Seperator

Product Info
GE IS200JGNDG1A
  • Warranty. 12/18 Months

Description

GROUND TERMINATION CARD (*12)
  • Model No. IS200JGNDG1A
Repair
GE - IS200JGNDG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes IS200JGNDG1A. ICC’s highly skilled technicians have the training and expertise to repair IS200JGNDG1A. In addition, our IS200JGNDG1A repairs come with a warranty. Please fill out our Request a Quote form with IS200JGNDG1A in the Subject Line, and/or include IS200JGNDG1A in the Message, for additional information about ICC’s IS200JGNDG1A. A ICC Business Development Leader will assist you with your IS200JGNDG1A needs shortly!

Reman
GE - IS200JGNDG1A

Purchasing a remanufactured GE IS200JGNDG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - IS200JGNDG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200JGNDG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - IS200JGNDG1A

IS200JGNDG1A is a Shield Ground Board manufactured and designed by General Electric as part of the Mark VI Series used in gas turbine control systems. The JGND board mounts next to the terminal board and offers easy ground connections for the customer's shield drain wires.

INSTALLATION:

JGND is mounted on a bracket made of sheet metal that is fastened to the plate holding the terminal board. With the two screws at each end of the terminal board, JGND is grounded to the bracket. Shield wires belonging to the customer are connected to terminals in the Euro-type terminal block. For a total of 48 ground connections, one or two JGND connectors can be placed on the side of the terminal board mounting bracket. At the positions of the board mounting screws, JGND offers a route to the sheet metal ground. A nylon washer is included in the standard mechanical assembly of this board to its mount between the board and the sheet metal.

As a result, JGND is separated from the sheet metal, enabling the board ground current to be wired into any desired grounding position. It is possible to channel ground currents into nearby sheet metal by removing the washer, which eliminates the need for extra grounding leads. When installing a JGND board, a decision must be made regarding whether to transmit ground currents directly to sheet metal or through a wire to a designated ground.

OPERATION:

The two grounding screws at the ends of JGND link all 24 connectors on the Euro block to the ground. These establish contact with the ground-connected metal mounting bracket. The board can be isolated using nylon washers, and ground currents can then be connected to any desired system position.

DIAGNOSTICS:

No diagnostics signals are obtained from the JGND Board

CONFIGURATION:

There are no jumpers or switches on JGND