GE IS200JPDDG1A

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - IS200JPDDG1A Seperator

Product Info
GE IS200JPDDG1A
  • Warranty. 12/18 Months

Description

DC PDM
  • Model No. IS200JPDDG1A
Repair
GE - IS200JPDDG1A Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes IS200JPDDG1A. ICC’s highly skilled technicians have the training and expertise to repair IS200JPDDG1A. In addition, our IS200JPDDG1A repairs come with a warranty. Please fill out our Request a Quote form with IS200JPDDG1A in the Subject Line, and/or include IS200JPDDG1A in the Message, for additional information about ICC’s IS200JPDDG1A. A ICC Business Development Leader will assist you with your IS200JPDDG1A needs shortly!

Reman
GE - IS200JPDDG1A

Purchasing a remanufactured GE IS200JPDDG1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - IS200JPDDG1A

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200JPDDG1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - IS200JPDDG1A

The IS200JPDDG1A is a DC Power Distribution Board developed by GE. It is a part of the Speedtronic Mark VIe control system. The DC power distribution board (JPDD) board is used to distribute a single DC power output to multiple loads. It can be used with a single input of 24 V, 48 V, or 125 V dc. Each load has a switch for maintenance purposes and fuses with local indicator light.

JPDDG1A has 15 A 5 x 20 mm (0.20 x 0.79 in) fuses for wire protection. JPDDG3A has empty fuse holders that accept a 31.75 x 6.35 mm (1.25 x 0.25 in) fuse.
Typical applications include DC relay and solenoid control power, and contact wetting. Each output includes a fuse, a switch, and a lamp to indicate the presence of output voltage. JPDD is not intended for power distribution to the I/O packs.
IS200JPDDG1A Inputs
Multiple JPDD boards can receive power from a single Main Power Distribution Module branch circuit. Power input can be either 125 V dc, 48 V dc, or 24 V dc nominal. Two 2-Pin Mate-N-Lok connectors are provided for 125 V dc power. One connector receives input power and the other can be used to distribute 125 V dc power to another JPDD board in a daisy chain fashion.
Two 4-pin Mate-N-Lok connectors are provided for 24/48 V dc power. These perform functions similar to those of the 2-pin connectors above. The 4-pin connector permits parallel connection of two pin-pairs for increased current capacity. It is expected that neither side of the dc power input is grounded.
Outputs
Six identical output circuits are provided. Each output circuit includes two fuses, a switch with a pair of isolation contacts on each side of the output, and a green lamp to indicate the presence of voltage across the output terminals.
The provision of a fuse and switch contact on each side of the DC path allows the use of this board with floating power sources.
Configuration
There are no jumpers on JPDD. Check the position of the six output load switches. It is possible to use other fuse ratings with this board to provide specific branch circuit ratings. A typical series of fuses that work with this board is the Bussmann ABC series of fuses with ratings from ¼ A through 15 A.
Fuses above 15 A shall not be used with this board. If alternate fuse ratings are used, the configuration of the board requires the insertion of the proper fuse in each branch circuit.
IS200JPDDG1A Installation
JPDD is held in a plastic holder, which mounts on a vertical DIN rail. When installing the JPDD, it is important to provide a ground lead from TB1 to the system ground. This creates a ground path for the metal switch bodies.
Power input can be 24 V dc, 48 V dc, or 125 V dc, but only one voltage level at any given time. Do not mix voltages. For cable destinations, refer to the circuit diagram. TB1 should be connected to the system ground.