GE IS200TTURH1B

Contact ICC to discuss your controls support requirements, ICC specialize in obsolete controls support offering repairs and spares
GE - IS200TTURH1B Seperator

Product Info
GE IS200TTURH1B
  • Warranty. 12/18 Months

Description

TERMINATION BD., TUR
  • Model No. IS200TTURH1B
Repair
GE - IS200TTURH1B Repair Lead Time:-
  • Standard Repair: 5-10 Business Days

ICC’s large inventory investment includes IS200TTURH1B. ICC’s highly skilled technicians have the training and expertise to repair IS200TTURH1B. In addition, our IS200TTURH1B repairs come with a warranty. Please fill out our Request a Quote form with IS200TTURH1B in the Subject Line, and/or include IS200TTURH1B in the Message, for additional information about ICC’s IS200TTURH1B. A ICC Business Development Leader will assist you with your IS200TTURH1B needs shortly!

Reman
GE - IS200TTURH1B

Purchasing a remanufactured GE IS200TTURH1B offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.

Exchange
GE - IS200TTURH1B

Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200TTURH1B and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty

Technical Specifications
GE - IS200TTURH1B

IS200TTURH1B is a Primary Turbine Protection Input terminal board developed by GE. TTUR has three relays, K25, K25P, and K25A, all of which must close in order to provide 125 V dc power to the main breaker, 52G. The JR5 connector is used for the speed signal cable to VTUR, and the JR1 connector is used for the other signals. Signals from TMR systems fan out to the JR5, JS5, JT5, JR1, JS1, and JT1 connectors.

Compatability

Terminal board is compatible with VTUR and features the following inputs and outputs:
Twelve passive pulse rate devices sensing a toothed wheel to measure turbine speed.
Generator voltage and bus voltage signals from potential transformers
125 V dc output to the main breaker coil for automatic generator synchronization

IS200TTURH1B Installation

TTUR Terminal Board Wiring, connect the wires for the magnetic pick-ups, shaft pick-ups, potential transformers, and breaker relays to the two I/O terminal blocks TB1 and TB2.
Each block is held together with two screws and has 24 terminals that accept wires up to #12 AWG. To the left of each terminal block is a shield termination strip connected to the chassis ground. Jumpers JP1 and JP2 are used to select SMX or TMR for relay drivers K25 and K25P.
Connect the wires for optional TTL active speed pick-ups to TB3 if they are used; these require an external power supply.

Operation

To measure turbine speed in simplex applications, up to four pulse rate signals can be used. TTUR receives generator and bus voltages for automatic synchronization with VTUR, the turbine controller, and the excitation system. TTUR controls the main breaker relay coil, 52G, and has permissive generator synchronizing relays.
All inputs in TMR applications fan to the three control racks. Control signals from R, S, and T are voted before they activate permissive relays K25 and K25P in TTUR. The VPRO and TREG boards control relay K25A.