Description
TRLYH1F PWR DIST DBICC’s large inventory investment includes IS200WPDFH1A. ICC’s highly skilled technicians have the training and expertise to repair IS200WPDFH1A. In addition, our IS200WPDFH1A repairs come with a warranty. Please fill out our Request a Quote form with IS200WPDFH1A in the Subject Line, and/or include IS200WPDFH1A in the Message, for additional information about ICC’s IS200WPDFH1A. A ICC Business Development Leader will assist you with your IS200WPDFH1A needs shortly!
Purchasing a remanufactured GE IS200WPDFH1A offers substantial savings over new/unused with the functionality and reliability to match. Our assurance in remanufactured products allows ICC to offer 24 Months Warranty.
Exchange is the combination of quick supply with applied discount against your old faulty card. Send us your old GE IS200WPDFH1A and we will replace (exchange) with a remanufactured spare, supplied with 24 Months Warranty
IS200WPDFH1A is a Power Distribution Board developed by GE. It is a part of Mark VIe control system. WPDFH is a TRLYH#F daughterboard that supplies power to the customer's solenoids. It has two power distribution circuits that can be used independently for 125 V dc, 115 V ac, or 24 V dc sources. Each section is made up of six fused branches that power the TRLYH#F terminal board. Each branch has its own voltage monitor across the secondary of its fuse pair. Each of these voltage detectors is fanned out to three independent open-collector drivers, which provide feedback to the R, S, and T I/O processors. The module should not be used in the absence of TRLY. Power is routed through this board to the TRLY terminal board points.
IS200WPDFH1A Features
As TRLY lacks power distribution, WPDF is added to provide a standard 125 V dc or 115 V ac source, or an optional 24 V dc source with individual fuses, for field solenoid power.
It includes a single fuse on the high side (pin 1 of J1-J4) of each power distribution circuit for alternating current applications where a fuse on the neutral return wire (pin 3 of J1-J4) is not desired.
To reduce confusion and mean time-to-repair in troubleshooting this highly interactive board set, the TRLY 1F/WPDF should be treated as the lowest replaceable unit (LRU) and replaced as a set when diagnostic messages indicate that either is involved.
If time and conditions allow, the individual failed board can be isolated further using golden boards to match with the individual suspect board.
Product Attributes
Number of Power Distribution Circuits (PDC): 2 each rated 10 A, nominal 115 V ac or 125 V dcim
Number of Fused Branches: 12: six for each PDC
Fuse rating: 3.15 A at 25 degrees Celsius, 2.36 A is the recommended maximum usage at 65 degrees Celsius
Voltage monitor, maximum response delay: 60 ms typical
Voltage monitor, minimum detection voltage: 16 V dc, 72 V ac
Voltage monitor, max current (leakage): 3 mA